Anybus X-gateway – Lonworks Slave - PROFIBUS Slave
The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between Lonworks and PROFIBUS networks.
FAST COPYING OF I/O DATA
The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as an Slave on both networks. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.
EASY CONFIGURATION - NO PROGRAMMING REQUIRED!
The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.
Features and benefits
- Fast copying of cyclic I/O data between two networks (10-15 ms)
- Proven and tested with all PLC manufacturers
- Supports up to a maximum of 512 bytes of Input and Output data in each direction
- Optional control and status information added to the I/O data for diagnostic purposes
- Robust stand-alone housing for use in harsh industrial environments
- Global free technical support and consultancy
Lonworks Slave interface
Lonworks network variables and configuration is made via an included configuration tool
- Certified for Lonmark application layer guidelines V3.2
- Lonworks network variables and configuration of the gateway is made via the included configuration tool (network commissioning requires 3rd part tools)
- Lonworks FT-X1 Transceiver
- Up to 256 input + 256 output LonWorks Network Variables / Modbus Word Registers
- Support for up to 15 nodes
- Amount and type of network variables configurable, data linking between Lonworks variables (SNVT's) and Modbus Registers
- Lonworks baudrate 78 kbit/s
- 1x D-sub 9-pin male RS-232 configuration port
- 1x 5-pin, 5.08 Phoenix network connector
PROFIBUS Slave interface
PROFIBUS Slave settings can be made either via on-board switches, or by importing the provided .GSD file into engineering tool of the controlling PLC.
- Complete PROFIBUS-DP/DPV1 Slave functionality according to extensions of EN 50170
- Supports Class 1 & Class 2 services
- Automatic baudrate detection up to 12Mbit/s
- Max. Cyclic I/O data 244 bytes Input and 244 bytes Output, max 344 bytes total (in+out)
- Acyclic User Parameter data / Diagnostics length - up to 237 bytes
- Supports PROFIBUS features: Sync and Freeze and Watchdog
- PROFIBUS slave settings via on-board switches or vis .GSD file
- 1x D-sub 9-pin female PROFIBUS connector
Technical specifications
| Dimensions (L•W•H) |
114 x 44 x 127mm or 4,49 x 1,73 x 5,00" |
| Weight |
400g or 0,880 lbs |
| Operating temperature |
-25 to +65 °C or -13 to +149 °F |
| Storage temperature |
-40 to +85 °C or -40 to +185 °F |
| Power supply |
24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector |
| Current consumption |
max. 400mA (Typical 200mA) |
| Enclosure material |
Aluminium and plastic |
| Installation position |
Vertical / Flat* |
| Galvanic isolation |
YES, on both BUS/Ethernet side |
| Mechanical rating |
IP20, NEMA rating 1 |
| Mounting |
DIN-rail (EN 50022 standard) |
| I/O configuration |
via USB port with Anybus Configuration Manager software |
| Certifications |
CE, CULUS, RoHS |