Anybus X-gateway – EtherNet/IP Scanner - PROFIBUS Slave
The Anybus X-gateway allows you to seamlessly inter-connect PLC control systems and their connected devices between EtherNet/IP and PROFIBUS networks.
FAST COPYING OF I/O DATA
The X-gateways primary function is with the fast transfer of cyclic I/O data between the two networks. This offloads your PLC from working with additional calculations. The gateway acts as a Scanner on the EtherNet/IP network and a Slave on the PROFIBUS network. The data transmission is completely transparent with a maximum data capacity of 512 bytes in each direction.
EASY CONFIGURATION - NO PROGRAMMING REQUIRED!
The connection between the two networks is quickly set up in the Anybus Configuration Manager software, included with the X-gateway. No programming skills are needed to set up the X-gateway. As factory default the X-gateways have a pre-defined I/O size of 20 bytes I/O.
Features and benefits
- Fast copying of cyclic I/O data between EtherNet/IP and PROFIBUS networks (10-15 ms)
- Proven and tested with all PLC manufacturers
- Powerful Scanner interface eliminates the need for a PLC controller on the EtherNet/IP network
- Supports up to a maximum of 512 bytes of Input and Output data in each direction
- Possibility to build web pages displaying and controlling a factory floor process with data from the other connected network
- Fast, dynamic transfer of fieldbus data to e.g. SCADA/HMI/Enterprise level systems based on Microsoft Windows, via the included Anybus OPC server
- Optional control status information added to I/O data for diagnostic purposes
- Robust stand-alone housing for use in harsh industrial environments
- Global free technical support and consultancy
EtherNet/IP Scanner/Master interface
An Anybus X-gateway with an integrated EtherNet/IP Scanner interface can be used when there is no existing EtherNet/IP controlling PLC. The X-gateway will perform EtherNet/IP Scanner functions.
- EtherNet/IP CONFORMANCE TESTED™ by ODVA
- Connects up 64 EtherNet/IP Adapter/Slaves
- 10/100Mbit operation in full or half-duplex
- Max. 509 bytes Input and 505 bytes Output data
- Optional Live List of the active status of the connected adapters
- Integrated FTP server provides easy file management using standard FTP clients.
- Web server with dynamic data capability and Server Side Include (SSI) capability
- Email client with dynamic data capability and Event-triggered email handling
- Support for CIP Objects
- DNS Capability
- TCP/IP settings via on-board DIP switches, DHCP/ARP/Anybus IPconfig (HICP)
- EtherNet/IP Scanner/Adapter network configuration via in-built web interface or RSLogix/Studio5000 software
- 1x RJ-45 Ethernet port
PROFIBUS Slave interface
PROFIBUS Slave settings can be made either via on-board switches, or by importing the provided .GSD file into engineering tool of the controlling PLC.
- Complete PROFIBUS-DP/DPV1 Slave functionality according to extensions of EN 50170
- Supports Class 1 & Class 2 services
- Automatic baudrate detection up to 12Mbit/s
- Max. Cyclic I/O data 244 bytes Input and 244 bytes Output, max 344 bytes total (in+out)
- Acyclic User Parameter data / Diagnostics length - up to 237 bytes
- Supports PROFIBUS features: Sync and Freeze and Watchdog
- PROFIBUS slave settings via on-board switches or vis .GSD file
- 1x D-sub 9-pin female PROFIBUS connector
Technical specifications
Dimensions (L•W•H) |
114 x 44 x 127mm or 4,49 x 1,73 x 5,00" |
Weight |
400g or 0,880 lbs |
Operating temperature |
-25 to +65 °C or -13 to +149 °F |
Storage temperature |
-40 to +85 °C or -40 to +185 °F |
Power supply |
24 VDC +/- 20% via 2-pole 5.08 mm Phoenix pluggable screw connector |
Current consumption |
max. 400mA (Typical 200mA) |
Enclosure material |
Aluminium and plastic |
Installation position |
Vertical / Flat* |
Galvanic isolation |
YES, on both BUS/Ethernet side |
Mechanical rating |
IP20, NEMA rating 1 |
Mounting |
DIN-rail (EN 50022 standard) |
I/O configuration |
via USB port with Anybus Configuration Manager software |
Certifications |
CE, CULUS, RoHS |