Operating Conditions
Temperature
0 to 55 °C (32 to 131 °F) ambient air temperature range
Shock
US MIL-STD-810C, method 516.2-1, procedure 1B (15 G, 11 ms half-sine pulse)
Vibration
Lloyd’s ENV2 test #1
Regulatory Compliance
North American:
CSA: CSA Listed for Class I, Division 2, Groups A, B, C, & D, T3A
(CSA Certificate 2314167)
European Compliance for CE Marking:
EMC Directive: Declared to Directive 2014/30/EU
Low Voltage Directive: Directive 2014/35/EU
ATEX Directive: Directive 2014/34/EU (Zone 2, Cat. 3, Group II G, Ex nA [nL] IIC T3 X)
Other European Compliance:
EAC Customs Union: Certified for use in Ordinary Locations only to Technical Regulation CU 004/2011 on the Safety of
Low Voltage Equipment and CU 020/2011 on the Electromagnetic Compatibility of Technical
Equipment Declaration of Conformity Registration No: RU C-US.АИ32.B.02262.
Marine Compliance
ABS: ABS Rules for Condition of Classification of Classification, Part 1, 2015 Steel Vessel Rules
DNV-GL: Standard for Certification No. 2.4, 2006: Temp. Class A, Hum. Class B, Vib. Class B, and EMC
Class A
LRS: Type Approval Test Specification No. 1, 2002, ENV1 and ENV2
Technical Manual
26166 (3 volumes)
MicroNet Plus™ Chassis
All versions are bulkhead mounted or adaptable to 19" (483 mm) rack mount back panel. Designed for control room environment.
MicroNet Plus™ with power supply section and 8 I/O slots
Dimensions
12.6" wide x 14.3" high x 12.1" deep (320 mm wide x 363 mm high x 307 mm deep)
Approximate Weight
35 lb (16 kg)
MicroNet Plus™ with power supply section and 14 I/O slots
Dimensions
18.8" wide x 14.3" high x 12.1" deep (478 mm wide x 363 mm high x 307 mm deep)
Approximate Weight
53 lb (24 kg)
Power Supply Input
18–36 Vdc, 100–150 Vac, 88–132 Vac (47–63 Hz), 180–264 Vac (47–63 Hz)